LTD DIFFERENTIAL PRESSURE TRANSMITTER
LTD DIFFERENTIAL PRESSURE TRANSMITTER
DESCRIPTION & FEATURES
- Designed to measure the differential pressures of liquids and gases
- Compact yet rugged stainless steel housing with highly accurate stainless steel sensor
- Available ranges from low pressure to 500 PSI (34.5 BAR)
- DIN-style electrical connection, cable outlet also available
- ±0.5% accuracy standard
- CE mark and RoHS compliant
- Electromagnetic protection
- 5 year warranty
Applications
Utilized to measure two varying and different pressures. Ideal for across-the-line filters, flow measurement, liquid tank levels and many other Commercial and Industrial applications.
SPECIFICATIONS
DOCUMENTS
DRAWINGS
FAQS
Parameter | Specification |
---|---|
Output Signal |
4-20 mA, 2 wire 0-5 Vdc or 0-10 Vdc 0…10 Vdc, 3-wire / Vs = 10-30 Vdc 0…5 Vdc, 3-wire / Vs = 10-30 Vdc 1...5 Vdc, 3-wire / Vs = 10-30 Vdc |
Accuracy | ±0.5% Full Scale Output |
Overload/Burst Pressure | 150% / 3 times |
Load Resistance | RL = (U-10)/0.02(Ω) (4~20mA current output), >20KΩ (voltage output) |
Long Term Stability | ±0.25% FSO (typically per year) |
Response Time | 1ms |
Storage Temperature | -10 to 70 deg C (14 to 158 deg F) |
Operating Temperature | -40 to 85 deg C (-40 to 185 deg F) |
Insulation Resistance | >100 MΩ @ 50 VDC |
Reverse Polarity Protection | Yes |
Electromagnetic Protection | EN50081-1/2, EN50082-2 |
Enclosure Rating | IP65 for DIN 43650-A, IP66 for Cable Outlet |
Housing | 1Cr18Ni9Ti |
Wetted Parts | 316L welded sensor |
Process Connections | 1/4” NPT Female or Male, G1/4 Female or Male |
Operation Life | 1 million cycles, minimum |
Lightning Protection | Yes |
Weight | 200 grams (0.4 pounds) |